Power Factor
0.8
Fair · 80.0%
Reactive Power
600 VAR
Phase Angle
36.87°
100% Private
All calculations run locally in your browser. Nothing is uploaded.
Power Factor Calculator finds power factor from real and apparent power online for free. Enter watts and VA to get power factor, reactive power, and phase angle.
Written & reviewed by Helperzy Editorial Team · Updated July 2026
Power Factor
0.8
Fair · 80.0%
Reactive Power
600 VAR
Phase Angle
36.87°
100% Private
All calculations run locally in your browser. Nothing is uploaded.
Type the real power the load actually consumes in watts. This is the energy doing useful work and forms the top of the power-factor ratio. It cannot exceed the apparent power.
Type the apparent power the source must supply in volt-amperes, the product of voltage and current. In reactive circuits this is larger than the real power. Apparent power must be greater than zero.
See the power factor, the reactive power in VAR, and the phase angle instantly. Aim for 0.95 or higher; below 0.8 usually justifies capacitor correction. Remember the tool reports magnitude only, not leading versus lagging.
Power factor measures how efficiently an AC circuit turns the power it draws from the supply into actual useful work. This calculator uses the core definition PF = Real Power (W) ÷ Apparent Power (VA), and returns a number between 0 and 1 along with the reactive power and phase angle. A power factor of 1.0 means every bit of supplied power does work, while a lower value means the source has to push extra current that ends up doing nothing useful — an inefficiency that costs money in commercial and industrial settings. The three quantities form what engineers call the power triangle. Real power (P), in watts, is the energy that genuinely does work like turning a shaft or heating an element. Apparent power (S), in volt-amperes, is simply the supply voltage multiplied by the current the source must deliver. Reactive power (Q), in volt-amperes reactive, is the part that sloshes back and forth between the source and reactive components without net work. They relate by S² = P² + Q², so the tool finds reactive power as Q = √(S² − P²). The phase angle between voltage and current is the arccosine of the power factor, and a lower power factor means a larger angle and a bigger reactive component. Here is a worked example. A motor draws 8,000 watts of real power while the supply must provide 10,000 VA of apparent power. The power factor is 8,000 ÷ 10,000 = 0.8, a fairly poor figure typical of an uncorrected motor. The reactive power is √(10,000² − 8,000²) = √(100,000,000 − 64,000,000) = √36,000,000 = 6,000 VAR, and the phase angle is arccos(0.8) ≈ 36.9 degrees. Correcting the power factor to 0.95 would cut the current the utility must supply for the same 8,000 watts of work. Put numbers on that too: at 0.95 the apparent power falls to 8,000 ÷ 0.95 = 8,421 VA, so on a 230-volt single-phase feed the current drops from 10,000 ÷ 230 = 43.5 amperes to 8,421 ÷ 230 = 36.6 amperes. Same useful output, seven fewer amps through every cable and contactor upstream. This matters most in factories and larger buildings. Motors, transformers, and fluorescent lighting are inductive loads that pull reactive current, raising apparent power without extra work, and utilities often bill penalties for low power factor because it forces them to supply more current. Facilities install capacitor banks to correct it, and engineers use these figures to size cables and transformers and to plan that correction. Some named cases: a textile unit whose meter shows 45 kW against 60 kVA works out a power factor of 0.75 and knows a penalty is coming, since most Indian state boards levy a surcharge below 0.90. A farm owner running a borewell pump adds a capacitor bank and watches the drawn current fall without the pump doing any less work. A data-centre planner sizing a UPS discovers the equipment must be rated in kVA rather than kW, because it is the apparent power the supply has to carry. A building manager comparing two chillers uses power factor to judge which one will load the incoming transformer less. The calculator guards the physics: apparent power must be above zero, real power cannot be negative, and real power cannot exceed apparent power since that is impossible. As a rule of thumb, 0.95 or higher is excellent, 0.9 and up is good, and below 0.8 usually warrants correction. Note that this tool works with magnitudes only, so it does not distinguish leading (capacitive) from lagging (inductive) power factor — you infer that from the load type. The mistake that catches people out is over-correcting: bolt on too much capacitance and the power factor swings leading, which raises voltage and can damage equipment just as surely as a poor lagging figure, so capacitor banks are normally switched in stages rather than fixed. Another trap is reading power factor at part load, since a motor running lightly loaded shows a far worse figure than the same motor at full load. Treat every result as an engineering estimate. Power-factor correction on mains or industrial supplies must follow your local electrical code and be designed and installed by a qualified electrician. All calculations run locally in your browser with nothing uploaded.
PF = P ÷ S Reactive power Q = √(S² − P²) Phase angle = arccos(PF) P = real power in watts (the part that does useful work) S = apparent power in volt-amperes (supply voltage × supply current) Q = reactive power in volt-amperes reactive (VAR) PF = power factor, a value between 0 and 1 Also true: S² = P² + Q², and S can never be smaller than P
Input
Real 8,000 W, Apparent 10,000 VA
Result
PF = 0.8, Q = 6,000 VAR, ≈ 36.9°
8000 ÷ 10000 = 0.8; √(10000² − 8000²) = 6000 VAR.
Input
Real 45,000 W, Apparent 60,000 VA
Result
PF = 0.75, Q = 39,686 VAR
45000 ÷ 60000 = 0.75, below the 0.90 threshold at which many utilities apply a surcharge.
Input
Real 950 W, Apparent 1,000 VA
Result
PF = 0.95 (excellent)
950 ÷ 1000 = 0.95, near-unity power factor.
Divide real power in watts by apparent power in volt-amperes: PF = W ÷ VA. The result is between 0 and 1. This calculator also gives the reactive power in VAR and the phase angle derived from the power triangle.
Ohm's Law Calculator solves voltage, current, resistance, and power online for free. Enter any two values to instantly get the other two.
Wattage Calculator finds power in watts from volts and amps online for free. Multiply voltage by current to get watts and kilowatts instantly.
Electricity Cost Calculator estimates the running cost of any appliance online for free. Enter watts, hours, days, and your rate to see daily and total cost.
Battery Life Calculator estimates how long a battery lasts online for free. Divide battery capacity in mAh by device current draw to get runtime in hours.
Image Resizer changes image dimensions online — set exact pixels, use percentage scaling, or pick from 12 presets (Instagram, Passport, YouTube, etc.). Target specific file sizes like 50KB or 100KB. Batch resize multiple images. 100% free, browser-based.
Image Converter changes images between any format online free — JPG, PNG, WebP, AVIF, PDF, ICO, BMP, HEIC, GIF, SVG. Batch conversion, resize, rotate, flip, AI format recommendation. 100% browser-based, no upload.
Convert JPG to WebP format online free — reduce image file size by 25-35% with identical visual quality. Batch conversion, adjustable quality, lossless mode available. Boost website speed and Core Web Vitals scores. 100% browser-based, no upload needed.
Convert PNG to WebP format online free — reduce file size by 26-34% while preserving full transparency. Batch conversion, lossless and lossy modes, adjustable quality. Boost website performance and Core Web Vitals. 100% browser-based, no upload needed.