Skip to main content

Free Voltage Drop Calculator – Wire Size, % Drop & Voltage at Load

Voltage Drop Calculator finds volts dropped, percentage drop and voltage at the load for copper or aluminium wire in AWG or mm², with a NEC 3%/5% pass-fail check.

Written & reviewed by Helperzy Editorial Team · Updated July 2026

NEC Ch. 9 Table 8@ 75 °CCopper & aluminiumAWG & mm²1φ / 3φ

Resistance from NEC Chapter 9 Table 8 at 75 °C. NEC recommends ≤3% for a branch circuit, ≤5% total. This method ignores conductor reactance (accurate for PF≈1 loads).

Voltage drop

7.78 V

3.38% of supply

Voltage at load

222.22 V

12 AWG · 6.4813 Ω/km

vs 3% (NEC)

FAIL

Try 10 AWG

Estimates only. Any mains wiring must follow your local electrical code and be done by a qualified electrician.

100% Private

Everything runs in your browser. Nothing is uploaded.

How to Use Voltage Drop Calculator

1

Choose the Circuit and Conductor

Pick single-phase or three-phase, then select copper or aluminium and whether your wire is sized in AWG or mm². Choose the exact conductor size from the list, which loads its ohms-per-kilometre resistance at 75 °C.

2

Enter Current, Length and Voltage

Type the load current in amps, the one-way run length in metres, and the source voltage. Set the percentage limit, which defaults to the NEC 3 percent branch recommendation, or enter a custom value for your local code.

3

Read the Result and Adjust

See the volts dropped, the percentage drop, the voltage remaining at the load, and whether it passes your limit. If it fails, the calculator suggests the next larger size, so raise the conductor or shorten the run and recheck.

How Voltage Drop Is Calculated and Why It Matters

A voltage drop calculator tells you how much voltage a cable loses along its length before the electricity reaches the load. Every conductor has resistance, and pushing current through that resistance uses up part of the supply voltage as heat. The longer the run and the higher the current, the bigger the loss, so a light or motor at the far end of a long cable sees less voltage than the panel it started from. Electricians, solar installers and anyone wiring a long garden or workshop run use this figure to decide whether a chosen wire size is adequate or whether they need thicker cable. The method here is the standard approximate one. For a single-phase or DC circuit the drop is Vd = 2 × L × I × R ÷ 1000, and for a balanced three-phase circuit it is Vd = √3 × L × I × R ÷ 1000. L is the one-way length in metres, I is the load current in amps, and R is the conductor resistance in ohms per kilometre. The factor of 2 in the single-phase case accounts for current travelling out and back along two conductors, while three-phase uses √3 (about 1.732) because of the phase geometry. Resistance values come from the NEC Chapter 9 Table 8 basis at 75 °C, which is why the calculator states the temperature — resistance rises with heat, and a table read at a different temperature is the usual reason two calculators disagree. Here is a worked case you can follow. Take 10 AWG copper, which is about 4.0773 Ω/km, carrying 15 amps over a 25 metre one-way run on a 120 volt single-phase supply. The drop is 2 × 25 × 15 × 4.0773 ÷ 1000 = 3.058 volts, which is 2.55 percent of 120 volts, leaving 116.94 volts at the load. Because 2.55 percent is below the NEC 3 percent branch-circuit recommendation, this run passes. Swap in a three-phase example: 50 mm² copper at 0.4193 Ω/km carrying 100 amps over 100 metres on 400 volts gives √3 × 100 × 100 × 0.4193 ÷ 1000 = 7.26 volts, only 1.82 percent, so it also passes comfortably. The results drive real decisions. A solar installer running DC from rooftop panels to a distant inverter checks that the drop stays low enough to avoid wasting harvested energy. A site electrician feeding a submersible pump 80 metres down a borehole confirms the motor still gets enough voltage to start under load. A caravan or boat builder sizing 12 volt wiring, where even a couple of volts lost is a large percentage, uses it to pick cable that keeps lights bright. When a run fails, the calculator suggests the next larger standard size that would pass, so you can size up without guesswork. A few limits are worth knowing. This model uses conductor resistance only and ignores reactance, so it is accurate for smaller cables and near-unity power factor loads but slightly optimistic for very large feeders and low power-factor motor loads. The NEC 3 percent branch and 5 percent total figures are recommendations in informational notes, not hard code limits, so a custom percentage lets you match IEC or local rules. The most common mistake is entering the round-trip length instead of the one-way length — this tool already doubles it for single phase, so give the one-way distance only. A second frequent slip is picking aluminium in the size list but reading a copper resistance from memory, since aluminium of the same size drops noticeably more voltage. Treat every answer as an engineering estimate: mains wiring must follow your local electrical code and be carried out by a qualified electrician. Everything runs in your browser, so nothing you enter is uploaded or stored.

Voltage Drop Calculator Formula & Method

Single phase / DC: Vd = 2 × L × I × R ÷ 1000 Three phase (balanced): Vd = √3 × L × I × R ÷ 1000 % drop = Vd ÷ Vsource × 100 Voltage at load = Vsource − Vd L = one-way conductor length in metres I = load current in amps R = conductor resistance in ohms per kilometre (NEC Ch. 9 Table 8 basis, 75 °C) √3 ≈ 1.732 (three-phase factor); 2 = out-and-back conductors (single phase)

Examples: Voltage Drop Calculator

Input

10 AWG copper, 15 A, 25 m one-way, 120 V single-phase (R = 4.0773 Ω/km)

Result

Vd = 3.06 V (2.55%), 116.94 V at load — PASS vs NEC 3%

Vd = 2 × 25 × 15 × 4.0773 ÷ 1000 = 3.058 V; 3.058 ÷ 120 × 100 = 2.55%; below the 3% branch recommendation.

Input

50 mm² copper, 100 A, 100 m, 400 V three-phase (R = 0.4193 Ω/km)

Result

Vd = 7.26 V (1.82%), 392.74 V at load — PASS

Vd = √3 × 100 × 100 × 0.4193 ÷ 1000 = 7.26 V; 7.26 ÷ 400 × 100 = 1.82%.

Input

12 AWG copper, 20 A, 30 m, 120 V single-phase (R = 6.4813 Ω/km)

Result

Vd = 7.78 V (6.48%) — FAIL vs 3%, size up

Vd = 2 × 30 × 20 × 6.4813 ÷ 1000 = 7.78 V; 6.48% exceeds 3%, so the tool suggests a larger conductor.

Frequently Asked Questions – Voltage Drop Calculator

The NEC recommends keeping voltage drop at or below 3 percent for a branch circuit and 5 percent for the combined feeder and branch. These are recommendations in informational notes, not hard limits, so many local codes and the IEC use similar or slightly different targets.